Goal Reached Thanks to every supporter โ€” we hit 100%!

Goal: 1000 CNY ยท Raised: 1336 CNY

100%

CVE-2021-26828 โ€” AI Deep Analysis Summary

Q1What is this vulnerability? (Essence + Consequences)

๐Ÿšจ **Essence**: ScadaBR allows **Remote Code Execution (RCE)** via file upload. ๐Ÿ’ฅ **Consequences**: Attackers can upload arbitrary JSP files and execute commands on the server, leading to full system compromise.

Q2Root Cause? (CWE/Flaw)

๐Ÿ›ก๏ธ **Root Cause**: Lack of effective **permission licensing** and **access control**. ๐Ÿ› **Flaw**: Inadequate validation when handling file uploads via `view_edit.shtm`, allowing malicious code injection.

Q3Who is affected? (Versions/Components)

๐Ÿ“ฆ **Affected**: Sensorweb ScadaBR. ๐Ÿ“… **Versions**: 0.9.1 (Linux) and through 1.0 / 1.12.4CE (Windows). โš ๏ธ **Note**: Older versions are primarily at risk.

Q4What can hackers do? (Privileges/Data)

๐Ÿ•ต๏ธ **Privileges**: Remote authenticated users. ๐Ÿ“‚ **Data/Action**: Can upload `.jsp` shells and execute **arbitrary code**. This grants full control over the underlying OS (Linux/Windows).

Q5Is exploitation threshold high? (Auth/Config)

๐Ÿ”“ **Threshold**: Medium. ๐Ÿ†” **Auth Required**: Yes, attackers need **valid credentials** (User/Pass) to access the upload interface. It is not fully unauthenticated.

Q6Is there a public Exp? (PoC/Wild Exploitation)

๐Ÿ”ฅ **Exploitation**: High. ๐Ÿ“œ **Public PoCs**: Multiple scripts available (e.g., `WinScada_RCE.py`, `LinScada_RCE.py`, `ScadaFlare`). ๐ŸŒ **Active**: Exploits are widely shared on GitHub.

Q7How to self-check? (Features/Scanning)

๐Ÿ” **Self-Check**: Scan for ScadaBR instances. ๐Ÿงช **Test**: Use provided POC scripts with valid credentials to attempt JSP upload via `view_edit.shtm`. ๐Ÿ“ก **Monitor**: Look for unauthorized JSP file uploads in logs.

Q8Is it fixed officially? (Patch/Mitigation)

๐Ÿฉน **Fix**: Upgrade to a patched version > 1.12.4CE. ๐Ÿ“ **Official**: The vendor (Sensorweb) has acknowledged the issue; check their official forum or release notes for the specific patch.

Q9What if no patch? (Workaround)

๐Ÿšง **Workaround**: If patching is impossible, **restrict network access** to the ScadaBR interface. ๐Ÿ”’ **Mitigate**: Enforce strong **MFA** and limit user privileges to prevent unauthorized upload access.

Q10Is it urgent? (Priority Suggestion)

โšก **Urgency**: High. ๐Ÿšจ **Priority**: Critical for SCADA environments. Even though auth is required, the impact (RCE) is severe. Patch immediately or isolate the system.