Vulnerability Information
Although we use advanced large model technology, its output may still contain inaccurate or outdated information.Shenlong tries to ensure data accuracy, but please verify and judge based on the actual situation.
Vulnerability Title
N/A
Vulnerability Description
miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not properly handle URIs beginning with a 0xfa character, which allows remote attackers to read data from arbitrary memory locations or cause a denial of service (application crash) via a crafted POST request.
CVSS Information
N/A
Vulnerability Type
N/A
Vulnerability Title
Siemens SIMATIC WinCC HMI Web服务器拒绝服务漏洞
Vulnerability Description
Siemens SIMATIC WinCC Flexible是一款集成了SIMATIC STEP 7、SIMATIC WinCC和SINAMICS StartDrive的工程设计软件平台。 Siemens SIMATIC WinCC多个版本中存在漏洞,该漏洞源于HMI web服务器内的miniweb.exe未能正确处理以0xfa 字符开始的URLs。远程攻击者可利用此漏洞借助特制POST请求,从任意内存地址中读取数据或造成拒绝服务(应用程序崩溃)。这些版本包括:Siemens WinCC flexible
CVSS Information
N/A
Vulnerability Type
N/A