An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. An unauthenticated remote OS Command Injection vulnerability allows an attacker to execute arbitrary commands on the RTU due to the passing of unsafe user supplied data to the RTU's system shell. Functionality in mobile.php provides users with the ability to ping sites or IP addresses via Mobile Connection Test. When the Mobile Connection Test is submitted, action.php is called to execute the test. An attacker can use a shell command separator (;) in the host variable to execute operating system commands upon submitting the test data.
CVSS Information
N/A
Vulnerability Type
N/A
Vulnerability Title
Mitsubishi Electric smartRTU和Inea ME-RTU 操作系统命令注入漏洞
Vulnerability Description
Mitsubishi Electric smartRTU是日本Mitsubishi Electric公司的一款智能远程终端单元(RTU)。Inea ME-RTU是斯洛文尼亚Inea公司的一款智能通信网关产品。 Mitsubishi Electric smartRTU 2.02及之前版本和INEA ME-RTU 3.0及之前版本中存在操作系统命令注入漏洞。该漏洞源于外部输入数据构造操作系统可执行命令过程中,网络系统或产品未正确过滤其中的特殊字符、命令等。攻击者可利用该漏洞执行非法操作系统命令。