目标达成 感谢每一位支持者 — 我们达成了 100% 目标!

目标: 1000 元 · 已筹: 1000

100.0%
获取后续新漏洞提醒登录后订阅
一、 漏洞 CVE-2021-27196 基础信息
漏洞信息

对漏洞内容有疑问?看看神龙的深度分析是否有帮助!
查看神龙十问 ↗

尽管我们使用了先进的大模型技术,但其输出仍可能包含不准确或过时的信息。神龙努力确保数据的准确性,但请您根据实际情况进行核实和判断。

Vulnerability Title
Specially Crafted IEC 61850 Protocol Sequence Vulnerability
来源: 美国国家漏洞数据库 NVD
Vulnerability Description
Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces. This issue affects: Hitachi ABB Power Grids Relion 670 Series 1.1; 1.2.3 versions prior to 1.2.3.20; 2.0 versions prior to 2.0.0.13; 2.1; 2.2.2 versions prior to 2.2.2.3; 2.2.3 versions prior to 2.2.3.2. Hitachi ABB Power Grids Relion 670/650 Series 2.2.0 versions prior to 2.2.0.13. Hitachi ABB Power Grids Relion 670/650/SAM600-IO 2.2.1 versions prior to 2.2.1.6. Hitachi ABB Power Grids Relion 650 1.1; 1.2; 1.3 versions prior to 1.3.0.7. Hitachi ABB Power Grids REB500 7.3; 7.4; 7.5; 7.6; 8.2; 8.3. Hitachi ABB Power Grids RTU500 Series 7.x version 7.x and prior versions; 8.x version 8.x and prior versions; 9.x version 9.x and prior versions; 10.x version 10.x and prior versions; 11.x version 11.x and prior versions; 12.x version 12.x and prior versions. Hitachi ABB Power Grids FOX615 (TEGO1) R1D02 version R1D02 and prior versions. Hitachi ABB Power Grids MSM 2.1.0 versions prior to 2.1.0. Hitachi ABB Power Grids GMS600 1.3.0 version 1.3.0 and prior versions. Hitachi ABB Power Grids PWC600 1.0 versions prior to 1.0.1.4; 1.1 versions prior to 1.1.0.1.
来源: 美国国家漏洞数据库 NVD
CVSS Information
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
来源: 美国国家漏洞数据库 NVD
Vulnerability Type
N/A
来源: 美国国家漏洞数据库 NVD
Vulnerability Title
ABB Relion 输入验证错误漏洞
来源: 中国国家信息安全漏洞库 CNNVD
Vulnerability Description
ABB Relion 670 Series是瑞士ABB公司的一款输电保护控制设备。 Relion 670, 650, and SAM600-IO; REB500; RTU500; FOX615 (TEGO1) 存在安全漏洞,攻击者可以利用该漏洞强制设备重新启动,从而导致设备在大约60秒钟内无法操作。 接口的产品。
来源: 中国国家信息安全漏洞库 CNNVD
CVSS Information
N/A
来源: 中国国家信息安全漏洞库 CNNVD
Vulnerability Type
N/A
来源: 中国国家信息安全漏洞库 CNNVD
受影响产品
厂商产品影响版本CPE订阅
-n/a n/a -