Vulnerability Information
Although we use advanced large model technology, its output may still contain inaccurate or outdated information.Shenlong tries to ensure data accuracy, but please verify and judge based on the actual situation.
Vulnerability Title
Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series
Vulnerability Description
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).
CVSS Information
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Vulnerability Type
输入验证不恰当
Vulnerability Title
Hitachi Energy Relion 输入验证错误漏洞
Vulnerability Description
Hitachi Energy Relion是瑞士日立能源(Hitachi Energy)公司的用于保护,控制,测量和监视为电力系统。 Hitachi Energy RTU500 series 存在安全漏洞,该漏洞源于 IEC 60870-5-104 功能中的 APDU 解析器中存在不正确的输入验证。
CVSS Information
N/A
Vulnerability Type
N/A