Honeywell Experion PKS Safety Manager through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0051, there is a Honeywell Experion PKS Safety Manager multiple proprietary protocols with unauthenticated functionality issue. The affected components are characterized as: Honeywell Experion TCP (51000/TCP), Safety Builder (51010/TCP). The potential impact is: Manipulate controller state, Manipulate controller configuration, Manipulate controller logic, Manipulate controller files, Manipulate IO. The Honeywell Experion PKS Distributed Control System (DCS) Safety Manager utilizes several proprietary protocols for a wide variety of functionality, including process data acquisition, controller steering and configuration management. These protocols include: Experion TCP (51000/TCP) and Safety Builder (51010/TCP). None of these protocols have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocols in question. An attacker capable of invoking the protocols' functionalities could achieve a wide range of adverse impacts, including (but not limited to), the following: for Experion TCP (51000/TCP): Issue IO manipulation commands, Issue file read/write commands; and for Safety Builder (51010/TCP): Issue controller start/stop commands, Issue logic download/upload commands, Issue file read commands, Issue system time change commands. A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.
CVSS Information
N/A
Vulnerability Type
N/A
Vulnerability Title
Honeywell Safety Manager 访问控制错误漏洞
Vulnerability Description
Honeywell Safety Manager是美国霍尼韦尔(Honeywell)公司的用于最大限度地减少事故、最大限度地延长生产正常运行时间、降低合规成本并管理工厂安全。 Honeywell Safety Manager 所有版本存在访问控制错误漏洞,该漏洞源于使用了安全构建器协议,该协议没有本地身份验证,攻击者利用该漏洞能够更改系统配置。
CVSS Information
N/A
Vulnerability Type
N/A